H1z2z2-k Solar PV Cable
Application
The solar cable intended for the interconnection within photovoltaic systems such as solar panel arrays. Suitable for fixed installations, internal and external, within conduit or systems, but not direct burial applications. It is UV resistance, wears resistance, and aging resistance, and the service life is more than 25 years.
Constrution
Characteristics
Rated voltage | DC 1500V / AC 1000V |
Temperature Rating | -40°C to +90°C |
Maximum Permitted DC Voltage | 1.8 kV DC (conductor/conductor, non earthed system, circuit not under load) |
Insulation Resistance | 1000 MΩ/km |
Spark Test | 6000 Vac (8400 Vdc) |
Test voltage | AC 6.5kv 50Hz 5min |
Standards
Ozone Resistance: According to EN 50396 part 8.1.3 Method B
Weathering- UV Resistance: According to HD 605/A1
Acid & Alkaline Resistance: According to EN 60811-2-1 (Oxal acid and sodium hydroxide)
Flame retardant: According to EN 50265-2-1, IEC 60332-1, VDE 0482-332-1-2, DIN EN 60332-1-2
Low smoke emission: According to IEC 61034, EN 50268
Halogen free: According to EN 50267-2-1, IEC 60754-1
Low corrosivity of gases: According to EN 50267-2-2, IEC 60754-2
Parameters
No. Of cores x Construction (mm2) |
Conductor Construction (n / mm) |
Conductor No./mm |
Insulation Thickness (mm) |
Current Aarring Capacity (A) |
1x1.5 |
30/0.25 |
1.58 |
4.9 |
30 |
1x2.5 |
50/0.256 |
2.06 |
5.45 |
41 |
1x4.0 |
56/0.3 |
2.58 |
6.15 |
55 |
1x6 |
84/0.3 |
3.15 |
7.15 |
70 |
1x10 |
142/0.3 |
4 |
9.05 |
98 |
1x16 |
228/0.3 |
5.7 |
10.2 |
132 |
1x25 |
361/0.3 |
6.8 |
12 |
176 |
1x35 |
494/0.3 |
8.8 |
13.8 |
218 |
1x50 |
418/0.39 |
10 |
16 |
280 |
1x70 |
589/0.39 |
11.8 |
18.4 |
350 |
1x95 |
798/0.39 |
13.8 |
21.3 |
410 |
FAQ
Q: Can we have our logo or company name to be printed on your products or the package?
A: The OEM & ODM order is warmly welcome and we have fully successful experience in OEM projects. What's more, our R&D team will give you the professional suggestions.
Q: How does your company do regarding Quality Control?
A: 1)All raw material we selected the high quality one.
2)Professional & Skilful workers care every details in handling the producing.
3)Quality Control Department specially responsible for quality checking in each process.
Q: How can I get a sample to test your quality?
A: We can provide free samples for your test and checking, just need to bear the freight charge.